Cable Type RNEDAFLEX-XT (N)TSKCGEWOEU
Voltage rating: 8.7/15kV
Cross-section 3×35+2x(7×2.5)mm2+1x(12E9/125+25KON), (N)TSKCGEWOEU-8.7/15kV Crane Flexible Cable
Application for use with mobile crane, continuous mining machines or longwall loading machines, heavy duty
trailing where more flexibility is desired to its medium and high voltage cable.
Construction
1. conductor tinned copper of class 6, flexible stranded
2. Insulation based on high-quality EPR with improved
mechanical and electrical Ethylene Propylene
Rubber (EPR)
3. Inner semiconductor Ethylene Propylene Rubber (EPR) same as
insulation, black color
4. Outer semiconductor extruded NBR of Easy Strip plan
5. Ground conductor mixed braid of tinned copper wires and Kevlar
aramid yarn to conduct earth and impart superior
tensile and torsional resistance. each braid has
25/2 sqmm.
6. Inner sheath compounds based on PCP
7. Anti-torsional braid Kevlar braid of high-strength, embedded in the
sheath
8. Central support Kevlar semiconductive rubber cradle seperator
with Kevlar polyester rope centered
9. Outer sheath special compounds based on PCP with excellent
strength and anti-abrasion characteristics, red
color
10. Control cores tinned copper strand with HEPR insulation,
Kevlar polyester rope centered and Kevlar
spinning around the 7×2.5 group
11. Fiber optical fiber optic unit with ETFE sheathed and Kevlar
threads reinforced with max. tensile load up to 1600N.
Technical data
Outer diameter: 59mm
Weight approx.: 4900±3% kg/km
Max.tensile load: 4200N
Max.conductor resistance: 0.565Ω/km(@20℃ )
Current-carrying capacity: 162A (@30℃ )
Standard: DIN VDE 0250-813
CU figure: 1450.60 kg/km
Electrical parameters
Rated voltage: 8.7/15 kV
Max. permissible operating voltage AC : 10.4/18 kV
Max. permissible operating voltage DC: 13.5/27 kV
AC Test Voltage: 24 kV (5min.)
Thermal parameters
Max. permissible temperature at conductor Max. short circuit temperature of the conductor Ambient temperature for fixed installation Ambient temperature in fully flexible operation |
90 °C 250 °C min -50 °C ;max +80 °C min -40 °C ;max +80 °C |
Mechanical parameters
Max. tensile load on the conductor: 25 N/mm²
Torsional stress: ± 50 °/m
Min. bending radius: 12 x D(reeling), 6 x D(static)
Travel speed Reeling operation: 180 m/min
Chemical parameters
Resistance to fire similar to: IEC 60332-1
Water resistance suitable for permanent use in water up to 50 meter diving depth. special
water such as rain should be upon request.